Fire Detection System · Safety Source Ltd

Input/Output Module

Official Safety Source Ltd catalogue listing for Input/Output Module.

Request product details

Verified source details

Provider
Safety Source Ltd
Category
Fire Detection System
Specifications
Specification Details Product FW821 Input-Output Module Type Intelligent Addressable I/O Module Function 1 × 24VDC Output & 1 × Feedback Input Monitor Addressing Occupies 1 address on SLC/DCL Certification UL 864 & ULC-S527 Listed Nominal Voltage (SLC/DCL) 24 VDC Voltage Range (SLC/DCL) 15 – 28 VDC Standby Current 0.15 mA Active Current (SLC/DCL) 0.26 mA Output Active Current 80 mA, 0.35 pf External Power Supply 24VDC (15.4 – 24.4VDC range) Output Voltage Range 15.0 – 24.0VDC (FW106 Aux) / 20.0 – 25.9VDC (Regulated PSU) Line Monitoring Open, short, ground fault & power loss detection Max Line Impedance Input: 25Ω / Output: 1Ω Max Ground Impedance 6.6 KΩ Compatible EOL Resistor FW421 (10KΩ) LED Indication Long blink (output active), Double blink (feedback), 4-sec blink (normal) Operating Temperature 0°C to 49°C (32°F to 120°F) Humidity 0 – 93% RH Mounting FW800 / FW801 box Dimensions 120 × 120 × 45 mm Weight 261 g (with backbox) Wiring Gauge 12 – 18 AWG
Verification
VERIFIED

Source record: provider website

Need a fit check?

We won’t guess at specifications.

Share the application, quantity, or project context and the team can review what is available.